RSB5-63 Miniature Circuit Breaker (RSB5 Air Switch)
I. Application Scope
The RSB5-63 miniature circuit breaker (RSB5 air switch) is suitable for AC 50/60Hz circuits with a rated operating voltage up to 230V/400V and a rated current up to 63A. It is primarily used for overload and short-circuit protection of electrical circuits and equipment in modern buildings. Additionally, it can be used for infrequent operation and isolation of circuits.
Structural Features:
? Components: The RSB5-63 consists of a plastic housing, operating mechanism, contact arc extinguishing system, and trip mechanism.
? Materials: The housing is made of high-strength, flame-retardant plastic, ensuring impact resistance and lightweight properties. The operating mechanism components are crafted from high-strength plastic, providing reliability and minimizing rotational inertia for a rapid trip response during faults.
? Trip Mechanism: Includes a bimetallic thermal overload inverse time trip and an electromagnetic instantaneous trip for short-circuit protection.
? Arc Extinguishing System: Features a specially designed arc guide angle and arc chamber, offering excellent current-limiting characteristics.
Applications:
Ideal for lighting, distribution circuits, and equipment in office buildings, residences, and similar facilities. It can also serve as an infrequent circuit switch under normal conditions.
Compliance:
The product meets standards IEC 60898 and GB 10963.1 and has obtained both CCC (China Compulsory Certification) and CE (Conformité Européenne) certifications.
II. Model and Meaning
Model Poles (P) Trip Type Rated Current (A)
RSB5-63 1P, 2P, 3P, 4P B, C, D 1, 2, 3, 6, 10, 16, 20, 25, 32, 40, 50, 63
? Trip Types:
? B Type: 3In ~ 6In
? C Type: 5In ~ 10In
? D Type: 10In ~ 20In
III. Normal Operating and Installation Conditions
1. Ambient Temperature:
? Maximum: +40°C
? Minimum: -5°C
? Average (24h): ≤ +35°C
2. Altitude:
? Installation height ≤ 2000m.
3. Humidity:
? Maximum relative humidity: 50% at +40°C.
? Higher relative humidity allowed at lower temperatures (e.g., 90% at +20°C). Special measures should be taken to address occasional condensation caused by temperature changes.
4. Pollution Level:
? Level 2.
5. Installation Environment:
? Free from significant shock, vibration, and explosive media.
6. Mounting Method:
? Installed on a TH35-7.5 mounting rail.
7. Installation Category:
? Categories II and III.
8. Wiring:
? Suitable for connecting wires with a cross-sectional area of ≤ 25mm2.
? Tightened with screws at a torque of 2.0 N·m.
IV. Main Specifications and Technical Performance
1. Rated Current (In):
1A, 3A, 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A.
2. Poles:
? 1P (Single Pole), 2P (Double Pole), 3P (Triple Pole), 4P (Four Pole).
3. Trip Types:
? B Type: 3In ~ 6In
? C Type: 5In ~ 10In
? D Type: 10In ~ 20In
4. Mechanical and Electrical Life:
? Electrical Life: 4000 cycles under rated voltage and current, with a power factor of 0.85–0.9.
? Mechanical Life: 10,000 cycles.
V. Technical Parameters
Rated Short-Circuit Breaking Capacity:
Trip Type Rated Current (In) Breaking Capacity (A) Power Factor (COSΦ)
C 1 ≤ In ≤ 40 6000 0.65 ~ 0.70
C 40 < In ≤ 63 4000 0.75 ~ 0.80
D 1 ≤ In ≤ 63 4000 0.75 ~ 0.80
Overcurrent Protection Characteristics (30–35°C):
No. Trip Type Rated Current (In) Test Current (A) Time Expected Result Initial State
1 C, D All Values 1.13In t ≤ 1h No trip Cold
2 C, D All Values 1.45In t < 1h Trip Following Test
3 C, D ≤32 2.55In s < t < 60s Trip Cold
C, D >32 1s < t < 120s Trip Cold
4 C All Values 5In t ≤ 0.1s No trip Cold
D All Values 10In t ≤ 0.1s No trip Cold
5 C All Values 10In t ≤ 0.1s Trip Cold
D All Values 20In t ≤ 0.1s Trip Cold
Altitude Correction Factors:
Trip Type Rated Current (In) ≤2000m 2000–3000m ≥3000m Example
C, D 1–63A 1 0.9 0.8 At 3200m, In = 32A × 0.8 = 25.6A
For more detailed specifications, including tripping characteristics curves and temperature/altitude compensation factors, please contact us.
Previous article:RSB5-125-1P