RSB5L-63-4P
Product Introduction
RSB5L-F63 Series Residual Current Circuit Breaker (RCCB)

The RSB5L-F63 series residual current circuit breaker (hereinafter referred to as RCCB) is suitable for AC circuits with a frequency of 50Hz, rated voltage up to 400V, and rated current up to 50A. It is designed for residential and similar applications to provide leakage and overload protection, preventing fire or personal injury caused by leakage or electric shock. Additionally, it offers overvoltage protection against voltage surges caused by grid faults.

The RSB5L-F63 series RCCB is a current-operated electronic residual current circuit breaker, consisting of the RSB5 circuit breaker and a residual current trip unit. When leakage or electric shock occurs in the protected circuit, and the leakage current (I△) reaches the tripping value, the circuit breaker will immediately operate, cutting off the power supply. This ensures protection against leakage and electric shock. Furthermore, the RCCB also provides overload and short-circuit protection for the circuit.

The circuit breaker complies with the standards IEC61009-1:1996 and GB16917.1 “Residual Current Operated Circuit Breakers with Overcurrent Protection for Household and Similar Uses (RCBO) - Part 1: General Rules.”
Product details

Scope of Application


The RSB5L-F63 series Residual Current Circuit Breaker (RCCB) is suitable for circuits with AC 50Hz, rated voltage up to 400V, and rated current up to 50A. It is designed for residential and similar applications, offering protection against leakage and overload to prevent fires or personal injuries caused by leakage or electric shock. Additionally, it provides overvoltage protection against excessive voltage caused by grid faults.


The RSB5L-63 series RCCB is a current-operated electronic RCCB, composed of the RSB5 circuit breaker and a residual current trip unit. When a leakage or electric shock occurs in the protected circuit, and the leakage current (I△) reaches the operating value, the breaker will instantly disconnect the power supply. This ensures leakage and electric shock protection. The RCCB also offers overload and short-circuit protection for circuits.


The circuit breaker complies with standards IEC61009-1:1996 and GB16917.1 “Residual Current Operated Circuit Breakers with Overcurrent Protection for Household and Similar Uses (RCBO) - Part 1: General Rules.”


Normal Operating and Installation Conditions

? Altitude: ≤2000m.

? Ambient Air Temperature: Not exceeding +40°C or lower than -5°C, with a 24-hour average not exceeding +35°C.

? Humidity: At +40°C, the relative humidity must not exceed 50%. At lower temperatures, higher humidity is permissible (e.g., 90% at 20°C), accounting for condensation due to temperature changes.

? Installation Environment:

? Free from impact, vibration, or rain/snow intrusion.

? No explosive medium, and free from gases or conductive dust sufficient to corrode metal or damage insulation.

? Pollution Degree: 2.

? Installation Category: III.

? Electromagnetic Environment: Class B.

? External Magnetic Field: Should not exceed 5 times the Earth’s magnetic field in any direction.

? Mounting Method: Standard mounting rail (TH35-7.5). To be installed in distribution boxes, cabinets, or enclosures.

? Installation Orientation: Generally installed vertically, with a maximum inclination of ±5° from the vertical plane. The handle in the upward position indicates power-on.


Main Technical Parameters

? Rated Current: 6, 10, 16, 20, 25, 32, 40, 50, 63A.

? Rated Operating Voltage: 230/400V AC.

? Rated Insulation Voltage: 500V.

? Rated Residual Operating Current: 30, 50, 75, 100, 300mA.

? Tripping Indicator:

? The RSB5L includes a residual current tripping indicator.

? When the reset button pops up, it indicates a residual current trip.

? Manual Control:

? Overcurrent Fault: The circuit breaker and residual current device reset simultaneously.

? Leakage Fault: The residual current device resets first, followed by the circuit breaker.

? Mechanical Endurance: 10,000 cycles.

? Electrical Endurance: 2,000 cycles.


Wiring

? 6~32A: Suitable for wires up to 16mm2.

? 40~63A: Suitable for wires up to 25mm2.


Compliance and Certification

? Standards: IEC61009-1 / GB16917.1.

? Certification: CCC Certification.


Tripping Characteristics

? C-Curve:

? Protection for conventional loads and distribution cables.

? Instantaneous tripping range: 5~10 times In.

? D-Curve:

? Protection for high inrush current loads (e.g., transformers).

? Instantaneous tripping range: 10~14 times In.


Previous article:RSB5L-125-1P

Next article:RSB5L-63-3P

Contact us
  • 0851-25112211
  • Email:wxy1665@163.com
  • Address:Lvyuan Avenue, Meitan County, Zunyi City, Guizhou Province
Follow WeChat
Scan WeChat

WeChat
WhatsApp

WhatsApp
Online consultation

Service Hotline

0851-25112211

Contact Number

13639025767

Call me
TOP